 |
BM100
- Single Level Trip Amplifier - IEC61508 (typically
SIL2) |
|

This replaces the MIN100.
Function:
Single Level Trip Amplifier from a single process signal input.
The trip action can be arranged so that the Alarm condition
can be above (High Trip) or below (Low Trip) the set point,
and that the relay can be either normally energised to de-energise
in the Alarm condition (Fail-Safe), or normally de-energised
to energise in the Alarm condition (Non Fail-Safe).
Power supply: DC powered
| |
| |
Proof Test Interval |
| SIL Ratings |
1 year |
6 months |
| 4-20mA Input & High Alarm Trip |
SIL 2 |
SIL 2 |
| 4-20mA Input & Low Alarm Trip |
SIL 1 |
SIL 2 |
| 0-10vdc Input & High Alarm Trip |
SIL 2 |
SIL 2 |
| 0-10vdc Input & Low Alarm Trip |
SIL 1 |
SIL 2 |
| Other Inputs (see data sheet) & High Alarm Trip |
SIL 2 |
SIL 2 |
| Other Inputs (see data sheet) & Low Alarm Trip |
SIL 1 |
SIL 2 |
|
This summary applies to BM100's built in Fail Safe mode |
|
  |
|
 |
BD100
- Single Level Trip Amplifier - IEC61508 (typically
SIL2) |
|

This replaces the DIN100.
Function: Single Level Trip Amplifier from
a single process signal input. The trip action can be arranged
so that the Alarm condition can be above (High Trip) or below
(Low Trip) the set point, and that the relay can be either
normally energised to de-energise in the Alarm condition (Fail-Safe),
or normally de-energised to energise in the Alarm condition
(Non Fail-Safe).
Options include: Double Pole Change Over
relays
| Power supply: mains powered |
| |
Proof Test Interval |
| SIL Ratings |
1 year |
6 months |
| 4-20mA Input & High Alarm Trip |
SIL 2 |
SIL 2 |
| 4-20mA Input & Low Alarm Trip |
SIL 2 |
SIL 2 |
| 0-10vdc Input & High Alarm Trip |
SIL 2 |
SIL 2 |
| 0-10vdc Input & Low Alarm Trip |
SIL 2 |
SIL 2 |
| Other Inputs (see data sheet) & High Alarm Trip |
SIL 2 |
SIL 2 |
| Other Inputs (see data sheet) & Low Alarm Trip |
SIL 1 |
SIL 2 |
|
This summary applies to
BD100's built in Fail Safe mode |
|
  |
|
 |
BU191
- Flow Meter Single Level Trip Amplifier - IEC61508 (typically
SIL2) |
|
Function:
The BU191 is a universally powered Alarm Unit suitable for
use with a number of different VA Flowmeters. It can be
configured for use as a Low or a High Flow Alarm, as
required. Each different VA Flowmeter will require a
different sensor head for mechanical reasons but in all
cases the operation of the Alarm Unit is the same. The
sensor heads supplied come with 1M of cable for connection
to the Alarm Unit. The BU191 has an “Instrument Fault”
indication LED (Amber) which is triggered following loss of
power or loss of connection to the Head. This LED can only
be cleared by restoring power or replacing the head, passing
the float from the Alarm State to the Healthy State and
pressing the RESET button to initiate the Stable condition.
The BU191 incorporates a sensitivity adjustment to cater for
different VA Flowmeters.
| Power supply: universal |
| |
Proof Test Interval |
| SIL Ratings |
1 year |
1
month |
| With
BHRAGK41, BH1100 and BH1300 Sensor Heads |
SIL 2 |
SIL
3 |
|
|
|
 |
|
 |
A
Block - Single Level Trip Amplifier |
|
The A Block is becoming obsolete, therefore please
select below as appropriate:
| On new projects: |
A Block (DC Powered) is replaced by the
BM100 |
  |
|
A Block (Mains Powered) is replaced by the
BD100 |
  |
For spares purposes: While stocks last, the A Block and
other Alphabet Blocks will continue to be available. Alphabet
Availability
Function:
Single Level Trip Amplifier from a single process signal input.
The trip action can be arranged so that the Alarm condition
can be above (High Trip) or below (Low Trip) the set point,
and that the relay can be either normally energised to de-energise
in the Alarm condition (Fail-Safe), or normally de-energised
to energise in the Alarm condition (Non Fail-Safe).
Options include: a remote set-point potentiometer;
a variable trip differential; a ten-turn set-point potentiometer;
and an AC Current or Voltage input.
Power supply: mains powered

|
 |
T
Block - Single Level Trip Amplifier with Integral Two Wire Transmitter
Power Supply |
The T Block is becoming obsolete.
While stocks last, the T Block and
other Alphabet Blocks will continue to be available. Alphabet
Availability
Function:
Single Level Trip Amplifier that has an on-board transmitter
loop power supply. The T Block can be manufactured with either
a Low Trip set point (alarm condition below the set point)
or a High Trip set point (alarm condition above the set point)
and with the relay Fail Safe (energised to de-energise in
the alarm condition) or Non-Fail Safe (relay normally de-energised
to energise in the alarm condition).
Application Notes: The T Block is ideal for
use with the Lee-Dickens loop powered Relative Humidity and
Temperature transmitters or with the loop powered head mounting
Temperature transmitters detailed elsewhere in this catalogue.
Power supply: mains powered
|
 |
T100
- Single Level Trip Amplifier |
|
Function:
The T100 is a Single Level Trip Amplifier from a single process
signal input. The trip action can be arranged so that the
Alarm condition can be above (High Trip) or below (Low Trip)
the set point, and that the relay can be either normally energised
to de-energise in the Alarm condition (Fail-Safe), or normally
de-energised to energise in the Alarm condition (Non Fail-Safe).
Options include: a ten-turn set-point potentiometer;
a mA retransmitting output; a latching action on the trip
relay; an on-board transmitter power supply; a difference
between two RTDs input; and a DPDT relay instead of the SPCO
relay.
Power supply: mains or DC

|
 |
T130
- Dual Channel Single Level Trip Amplifier |
|
Function:
The T130 is a Dual Channel Single Level Trip Amplifier, i.e.
two Single Level Trip Amplifiers on the one board. The trip
action can be arranged so that the Alarm conditions can be
above (High Trip) or below (Low Trip) each of the set points,
and that the relays can be either normally energised to de-energise
in the Alarm condition (Fail-Safe), or normally de-energised
to energise in the Alarm condition (Non Fail-Safe).
Options include: remote set-point potentiometers;
and ten-turn set-point potentiometers.
Power supply: mains or DC
|
 |
BM120
- Dual Level Trip Amplifier - IEC61508 (typically SIL2) |
|
This replaces the MIN120.
Function:
Dual Level Trip Amplifier from a single process signal input.
The trip action can be arranged so that the Alarm condition
can be above (High Trip) or below (Low Trip) each of the set
points, and that the relays can be either normally energised
to de-energise in the Alarm condition (Fail-Safe), or normally
de-energised to energise in the Alarm condition (Non Fail-Safe).
Power supply: DC powered
| |
| |
Proof Test Interval |
| SIL Ratings |
1 year |
6 months |
| 4-20mA Input & High Alarm Trip |
SIL 2 |
SIL 2 |
| 4-20mA Input & Low Alarm Trip |
SIL 1 |
SIL 2 |
| 0-10vdc Input & High Alarm Trip |
SIL 2 |
SIL 2 |
| 0-10vdc Input & Low Alarm Trip |
SIL 2 |
SIL 2 |
| Other Inputs (see data sheet) & High Alarm Trip |
SIL 2 |
SIL 2 |
| Other Inputs (see data sheet) & Low Alarm Trip |
SIL 1 |
SIL 2 |
|
This
summary applies to BM120's built in Fail Safe mode
Please note, that for High & Low Alarm trips, the
above SIL for Low Alarm Trip should be
used |
|
  |
|
 |
BD120
- Dual Level Trip Amplifier - IEC61508 (typically SIL2) |
|

This replaces the DIN120.
Function: Dual Level Trip Amplifier from a
single process signal input. The trip action can be arranged
so that the Alarm conditions can be above (High Trip) or below
(Low Trip) the set point, and that the relays can be either
normally energised to de-energise in the Alarm condition (Fail-Safe),
or normally de-energised to energise in the Alarm condition
(Non Fail-Safe).
Power supply: mains powered
| |
| |
Proof Test Interval |
| SIL Ratings |
1 year |
6 months |
| 4-20mA Input & High Alarm Trip |
SIL 2 |
SIL 2 |
| 4-20mA Input & Low Alarm Trip |
SIL 2 |
SIL 2 |
| 0-10vdc Input & High Alarm Trip |
SIL 2 |
SIL 2 |
| 0-10vdc Input & Low Alarm Trip |
SIL 2 |
SIL 2 |
| Other Inputs (see data sheet) & High Alarm Trip |
SIL 2 |
SIL 2 |
| Other Inputs (see data sheet) & Low Alarm Trip |
SIL 1 |
SIL 2 |
|
This
summary applies to BD120's built in Fail Safe mode
Please note, that for High & Low Alarm trips, the
above SIL for Low Alarm Trip should be
used |
|
  |
|
 |
AA
Block - Dual Level Trip Amplifier |
|
The AA Block is becoming obsolete, therefore please
select below as appropriate:
| On new projects: |
AA Block (DC Powered) is replaced by the
BM120 |
  |
|
AA Block (Mains Powered) is replaced by the
BD120 |
  |
For spares purposes: While stocks last, the AA Block and
other Alphabet Blocks will continue to be available. Alphabet
Availability
Function:
Dual Level Trip Amplifier from a single process signal input.
The trip action can be arranged so that the Alarm conditions
can be above (High Trip) or below (Low Trip) each of the set
points, and that the relays can be either normally energised
to de-energise in the Alarm condition (Fail-Safe), or normally
de-energised to energise in the Alarm condition (Non Fail-Safe).
Options include: remote set point potentiometers;
ten-turn set-point potentiometers; and an AC Voltage input.
Power supply: mains powered

|
 |
T120
- Dual Level Trip Amplifier |
|
Function:
The T120 is a Dual Level Trip Amplifier from a single process
signal input. The trip action can be arranged so that the
Alarm conditions can be above (High Trip) or below (Low Trip)
each of the set points, and that the relays can be either
normally energised to de-energise in the Alarm condition (Fail-Safe),
or normally de-energised to energise in the Alarm condition
(Non Fail-Safe).
Options include: remote set-point potentiometers;
and ten-turn set-point potentiometers, a mA retransmitting
output; a latching action on the trip relays; a difference
between two RTDs input; and DPDT relays instead of the SPCO
relays.
Power supply: mains or DC
|
 |
BM130
- Triple Level Trip Amplifier |
|
This replaces the MIN130.
Function:
Triple Level Trip Amplifier from a single process signal input.
The trip action can be arranged so that the Alarm condition can
be above (High Trip) or below (Low Trip) each of the set points,
and that the relays can be either normally energised to de-energise
in the Alarm condition (Fail-Safe), or normally de-energised to
energise in the Alarm condition (Non Fail-Safe).
Power supply: DC powered
|
 |
BD130
- Triple Level Trip Amplifier |
|
This replaces the DIN130.
Function:
Triple Level Trip Amplifier from a single process signal input.
The trip action can be arranged so that the Alarm condition
can be above (High Trip) or below (Low Trip) each of the set
points, and that the relays can be either normally energised
to de-energise in the Alarm condition (Fail-Safe), or normally
de-energised to energise in the Alarm condition (Non Fail-Safe).
Power supply: mains powered
|
 |
BM140
- Quadruple Level Trip Amplifier |
|
This replaces the MIN140.
Function:
Quadruple Level Trip Amplifier from a single process signal input.
The trip action can be arranged so that the Alarm condition can be
above (High Trip) or below (Low Trip) each of the set points, and
that the relays can be either normally energised to de-energise in
the Alarm condition (Fail-Safe), or normally de-energised to energise
in the Alarm condition (Non Fail-Safe).
Power supply: DC powered
|
 |
BD140
- Quadruple Level Trip Amplifier |
|
This replaces the DIN140.
Function:
Quadruple Level Trip Amplifier from a single process signal
input. The trip action can be arranged so that the Alarm condition
can be above (High Trip) or below (Low Trip) each of the set points,
and that the relays can be either normally energised to de-energise
in the Alarm condition (Fail-Safe), or normally de-energised to
energise in the Alarm condition (Non Fail-Safe).
Power supply: mains powered
|
 |
AL
Block - Single Level Latching Trip Amplifier |
|
Function:
Single Level Latching Trip Amplifier from a single process
signal input. Two separate set points allow for setting of the
trip set point at which point the relay will be latched and
the release set point at which the relay will be unlatched.
The AL Block can be manufactured with either a Low Trip set
point or a High Trip set point. In both cases as the signal
passes Down (for a Low Trip) or Up (for a High Trip) through
the trip set point the relay will be energised and will remain
energised until the signal passes back through the release set
point when it will be de-energised. The AL Block is ideally
suited to maintaining levels in a tank between two pre-set
levels either for filling using the Low Trip version or for
emptying using the High Trip version.
Power supply: mains powered

|
 |
Single
Level Trip Amplifier |
Function:
The BM9431 is a DIN rail mounting (TS35) Single Level
Trip Amplifier monitoring a 4 to 20mA input signal. It
has one process trip and additional internal alarm
relays/LEDs for "Out of Range Input" and
"Power OK/Fail".
The process trip can be configured as a Low or High
trip, as required. The trip amplifier is compliant with
NAMUR NE43, being able to detect faulty transmitters
whose outputs are below 3.8mA or above 20.5mA.
Optional DPCO Contacts on Process Trip.
Power supply: DC powered

|
 |
Dual
Level Trip Amplifier |
Function: The BM9432 is a DIN rail
mounting (TS35) Dual Level Trip Amplifier monitoring a 4
to 20mA input signal. It has two process trips and
additional internal alarm relays/LEDs for "Out of
Range Input" and "Power OK/Fail".
Each process trip can be configured as a Low or High
trip, as required. The trip amplifier is compliant with
NAMUR NE43, being able to detect faulty transmitters
whose outputs are below 3.8mA or above 20.5mA.
Power supply: DC powered

|
|